Medium performance power line filters (MP)
Medium performance power line filter
|

|
Technology
|
Mounting
These filters are designed to be mounted in derectly on the entry panel of a Faraday cage or in an shielded filter housing. Please contact us for options.
Torgue value max.
|
Ø M 27 |
: 40 Nm |
@ M 32 |
: 40 Nm |
|
Connection
Treaded terminals with nut
|
Ø M 4 |
: 1.2 Nm |
Ø M 6 |
: 2.45 Nm |
Ø M 8 |
: 10 Nm |
Ø M 10 |
: 15 Nm |
Ø M 12 |
: 20 Nm |
|
|
Models and ordering data
Reference
|
Current max.
|
Lines
|
Rated voltage UR
|
Operating temperature
|
Test voltage
|
Leakage current @250V/50Hz
|
Curve
|
(A)
|
Amount
|
VDC
|
VAC 50-60 Hz
|
VAC 400 Hz
|
ºC
|
VDC
|
(mA)
|
Structure
|
MP - 1050
|
50
|
1
|
1000
|
250
|
-
|
-40 +85
|
2121
|
86.4
|
1 
|
MP - 1075
|
75
|
1
|
440
|
250
|
-
|
-40 +85
|
800
|
812
|
2
|
MP - 1100
|
100
|
1
|
1000
|
250
|
125
|
-40 +85
|
2121
|
173
|
2
|
MP - 1100 type2
|
100
|
1
|
1000
|
250
|
-
|
-40 +65
|
2121
|
86.4
|
1 
|
MP - 1200
|
200
|
1
|
440
|
250
|
-
|
-40 +85
|
800
|
812
|
2
|
MP - 1200 type2
|
200
|
1
|
1000
|
250
|
-
|
-40 +65
|
2121
|
86.4
|
1 
|
MP - 1300
|
300
|
1
|
440
|
250
|
-
|
-40 +85
|
800
|
812
|
2
|
|
Attenuation characteristics
Structure 1 Attenuation on load (50 Ω) MIL STD 220 A or GAM T 21 |
 |
Structure 2 Attenuation on load(50 Ω) MIL STD 220 A or GAM T 21 |
 |
|
|
Dimensions in mm per filter
Current
|
A
|
B
|
C
|
Ø F
|
L
|
Weight (Gr.)
|
Structure
|
50 A
|
-
|
-
|
115
|
-
|
192
|
820
|
2
|
75 A
|
41
|
17
|
92
|
M6
|
166
|
670
|
1
|
100 A
|
48
|
24
|
92
|
M8
|
180
|
750
|
1
|
100 A type 2
|
-
|
-
|
122
|
-
|
199
|
850
|
2
|
200 A
|
49
|
25
|
92
|
M10
|
172
|
950
|
1
|
200 A type 2
|
-
|
-
|
140
|
-
|
217
|
940
|
2
|
300 A
|
59
|
35
|
92
|
M12
|
194
|
1050
|
1
|
|
Mechanical data
|
Structure 1 |
 |
Structure 2
|
 |
|
When you want to order a Medium performance power line filter then please mention the partnumber as follow: | |
 |
MP |  | 1 |  | 50 |
| | | | |
| | | | Please specify the rated current in Amp |
Download datasheets (PDF)