Medium performance power line filters (MP2)
Compact general purpose three-phase and neutral line EMC filter
- Three phase and neutral line filter for general purpose four-wire filtering
- Compact space-saving design
- Choice of connection style
- Low operating leakage current
Technical specifications
Maximum contious operating voltage |
3x 480/277VAC |
Operating frequency |
dc to 60Hz |
Rated currents |
8 to 160A @ 50ºC |
High potential test voltage |
P-> E 2650VDC for 2 sec |
P-> P 2100VDC for 2 sec |
Protection category |
IP20 |
IP00 (filters with connectors -28) |
Overload capability |
4x rated current at swith on, |
1.5x rated current for 1 minute, once per hour |
Temprature range (operation and storage) |
-25ºC to +100ºC (25/100/21) |
Flamability corresponding to |
UL 94V-2 or better |
Design corresponding to |
UL 1283, CSA 22.2 No. 8 1986, IEC/EN 60939 |
MTB @ 50ºC/400V (Mil-HB-217F) |
600.000 |
|
 |
Features and benefits
- The medium performance type 2 (MP2) filters are disigned specifically for application involving asymmetric loads, ranging from industrial controls to medical electronics systems. These typically involve insuffiently filtered converters and switch-mode power supplies on different phases, causing current imbalance and significant interferance problems.
- Employing single-stage filter circuits for each phase and the neutral line, MP2 filters provide high attenuation of both symetrical and asymmetrical interference.
- Used as meins input filter, MP2 filters alse increase conducted immunity and thus contribute to overallsystem reliability.
- Choice of connection style as well as filter ratings in line with common fuse values support a fast and easy application-specific filter selection and deployment.
- A light weith aluminium housing with a small footprint ensures that the filters can be easily accommodated on control panels and in tight power cabinets.
|
General applications
- General purpose four-wire filtering
- High-power office equipment
- Power suplies
- UPS
- Medical applications
- Electrical cabinets
- Control panels
|
Partnumber |
Rated current @50ºC (40ºC) [A] |
Leakage current** @ 400VAC/50Hz [mA] |
Power loss @ 25ºC/50Hz [W] |
Weigth
[kg] |
MP2-4008 |
8 |
3.4 |
2.7 |
0.8 |
MP2-4016 |
16 |
3.4 |
6.0 |
1.1 |
MP2-4025 |
25 |
3.4 |
11.6 |
1.4 |
MP2-4036 |
36 |
3.4 |
14.8 |
1.5 |
MP2-4064 |
64 |
3.4 |
18.4 |
2.2 |
MP2-4080 |
80 |
3.4 |
18.8 |
4.5 |
MP2-4120 |
120 |
3.4 |
25.1 |
6.1 |
MP2-4160 |
160 |
3.4 |
30.7 |
8.0 |
|
Dimensions
|
8A |
16A |
25A |
36a |
64A |
80A |
80A |
120A |
120A |
160a |
A |
120 |
160 |
130 |
130 |
140 |
160 |
160 |
180 |
180 |
200 |
B |
143 |
143 |
153 |
153 |
153 |
170 |
170 |
170 |
170 |
170 |
C |
80 |
80 |
115 |
115 |
125 |
110 |
110 |
130 |
140 |
130 |
D |
115 |
115 |
125 |
125 |
125 |
140 |
140 |
140 |
140 |
140 |
E |
80 |
80 |
90 |
90 |
100 |
110 |
110 |
130 |
130 |
150 |
F |
127.5 |
127.5 |
137.5 |
137.5 |
137.5 |
153.5 |
153.5 |
153.5 |
153.5 |
153.5 |
G |
6.5 |
6.5 |
6.5 |
6.5 |
6.5 |
6.5 |
6.5 |
6.5 |
6.5 |
6.5 |
H |
1 |
1 |
1 |
1 |
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
I |
18 |
18 |
18 |
18 |
18 |
30 |
39 |
30 |
45 |
30 |
J |
M6 |
M6 |
M6 |
M6 |
M6 |
M10 |
M10 |
M10 |
M10 |
M10 |
K |
12 |
12 |
13 |
13 |
13 |
17.5 |
17.5 |
17.5 |
17.5 |
17.5 |
L |
33 |
33 |
50 |
50 |
50 |
30 |
30 |
30 |
30 |
30 |
|
Technical drawings
MP2-4008 till MP2-4064 (8A till 64A) versions

MP2-4080 till MP2-4160 (80A till 160A) versions

|
Attenuation curve Per CISPR 17;
A : 50Ω/50Ω sym; B : 50Ω/50Ω asym; C : 0.1Ω/100Ω sym; D : 100Ω/0.1Ω sym;
Attenuation MP2-4008 (8A type)

Attenuation MP2-4016 (16A type)

Attenuation MP2-4025 (25A type)

Attenuation MP2-4036 (36A type)

Attenuation MP2-4064 (64A type)

Attenuation MP2-4080 (80A type)

Attenuation MP2-4120 (120A type)

Attenuation MP2-4160 (160A type)

|
When you want to order a Medium performance power line filter type 2 please mention the partnumber as follow:
| |
 |
MP2 |  | 4 |  | 080 |
| | | | |
| | | | Please specify the rated current in Amp
|