The SP (Standard performance) filters provide filtering for frequency inverters and variable speed motor drives. Designed for very noisy applications, they attenuate conducted interference at low and high frequency ranges and protect programmable logic controllers from RF noise on the AC power line. These filters perform best when installed on the line side of the motor drive. The SP filters better prevent noise from returning to the line, enabling equipment to meet strict European regulations on RFI.
Suited for field wiring applications, these filters are ideal for EMC troubleshooting and field refurbishing. The filters could also be sold as an accessory to motor drives marketed Worldwide.
General specifications
-
High performance single phase filter
-
Suitable to meet latest EMC standards (EN55011, -14, UL 1283 and EN133200)
-
Applicable in single phase-powered FC-drives with ling motor-cables
-
Very high insertion loss
-
Double stage design
-
Shock protected screw type terminals
-
Ideal for EMC-trouble shootin and EMC-refurbishing in the field
|
Mounting
These protections are designed for mounting on the penetration panel or directly on the non-painted wall of the Faraday cage. The SP power line filters feature side flanges for easy mounting and DIN type terminals which eliminate live metal parts, allowing safer and easier connection.
|
|
Typical applications
- Frequency inverters
- Variable speed motor drives
|
|
Technical specifications
Maximum leakage current, each line-to-ground
|
@ 120 VAC 60 Hz |
: 3.8 mA |
@ 250 VAC 50 Hz |
: 6.7 mA |
Hipot rating (One minute) |
line-to-ground |
: 2250 VDC |
line-to-line |
: 1450 VDC |
Operating frequency |
: 50/60 Hz |
Rated voltage (max.) |
: 250 VAC |
|
|
Models and ordering data
Reference
|
rated Current
|
Connection
|
Inductance
|
Leakage current @250V/50Hz
|
(A)
|
Type
|
(L)
|
(mA)
|
SP2 - 2003
|
3
|
Terminal block 4mm2
|
8,8 mH
|
5,2
|
SP2 - 2006
|
6 |
Terminal block 4mm2
|
5,6 mH
|
5,2
|
SP2 - 2020
|
20
|
Terminal block 4mm2
|
5,5 mH
|
5,2
|
*See "Mechanical data" pictures below
|
|
Attenuation characteristics
(Red = Asym. / Grey = Sym)
|
Dimensions in mm
Reference
|
A
|
B
|
C
|
D
|
E
|
F
|
SP-2006
|
116.8
|
78.7
|
45.21
|
67.8
|
94.0
|
50.8
|
SP-2012
|
151.3
|
100.6
|
55.4
|
88.9
|
114.8
|
50.8
|
SP-2016
|
151.3
|
100.6
|
55.4
|
88.9
|
114.8
|
50.8
|
SP-2025
|
175.5
|
139.2
|
64.77
|
124.5
|
150.9
|
70.0
|
SP-2036
|
175.5
|
139.2
|
64.77
|
124.5
|
150.9
|
70.0
|
SP-2050
|
175.5
|
139.2
|
64.77
|
124.5
|
150.9
|
70.0
|
|
Mechanical data
|
(Front view and top view, see dimension table) (SP-2006, SP-2012, SP-2025) |
  |
(Side view) (SP-2025, SP-2036, SP-2050)
|
 |
(Bottom view) (SP-2025, SP-2036, SP-2050)
|
 |
|
When you want to order a Standard performance power line filter type 2 please mention the partnumber as follow:
| |
 |
SP2 |  | 2 |  | 020 |
| | | | |
| | | | Please specify the rated current in Amp
|